By Nikola Marinko · Head of Project and Service Execution, Siemens DI Serbia · Updated November 2026 · 12 min read
Six pumps at a new plant, each on its own drive in the motor control centre, and the cables to the furthest ones run between 175 and 200 metres. The drives were already built into the panels when I went through the feeder list, so the question was a practical one: does an 11 kW drive with a C2 filter in its order code still do what the order says at that length? This page works through one real feeder the way I would check it before anything is ordered.
The cable itself is the easy part. A shielded 3x10 mm² copper cable carries the 21.7 A the motor draws with a wide margin, and the voltage drop at 180 m comes out near 3.2 %, inside the 5 % of IEC 60364-5-52 Annex G. The harder part is what the drive does to that cable. A VFD switches the output thousands of times a second, and every edge pushes a small current through the cable capacitance into earth. The longer the cable, the larger that current. The C2 EMC filter keeps it inside the drive and out of the supply network, and it is rated for 150 m of shielded motor cable, while the drive itself accepts 200 m. Between those two numbers sits the decision.
The page shows it with diagrams you can move: the pulse train, the common-mode loop through the cable shield, an explorer that recalculates current and loss as you drag the length, and the cables a pump needs besides the power cable, the motor PTC and the local control station. It ends with ranked options, starting with keeping the filter on every drive. The same check is built into the free cable sizing calculator on this site, and the other Project Delivery notes, the PMP guide included, come from the same projects.
Project Delivery · Cable sizing calculator · PMP guide · All 12 projects · Field stories
VFD Cable Length and the C2 EMC Filter: 180 m to an 11 kW Pump
WORKED EXAMPLE